Description
Model | EnergyCell 200NC |
Cells Per Unit | 6 |
Voltage Per Unit | 12 Vdc |
Operating Temperature Range (with temperature compensation) | Discharge: -40°F (-40°C) to 160°F (71°C) Charge: -10°F (-23°C) to 140°F (60°C) |
Optimal Operating Temperature Range | 74°F (23°C) to 80°F (27°C) |
Recommended Maximum Charging Current Limit Per String | 53 Adc |
Float Charging Voltage | 13.62 Vdc / unit average at 77°F (25°C) |
Equalization and Cycle Service Charging Limits | 14.4 Vdc / unit average at 77°F (25°C) |
Self Discharge | Battery can be stored up to 6 months at 77°F (25°C) before a freshening charge is required. Batteries stored at temperatures greater than 77°F (25°C) will require recharge sooner than batteries stored at lower temperatures. |
Temperature Compensation Factor (Charging) | 5mV per degree C per cell (2V) |
Terminal | Threaded copper alloy insert Terminal to accept ¼-20 UNC bolt |
Terminal Hardware Initial Torque | 110 in-lbs (12.4 Nm) |
Weight (lbs/kg) | 131 / 60 |
Dimensions H x D x W (in/cm)* | 12.60 x 22.01 x 4.95 / 32.0 x 55.09 x 12.6 |